Skip to main content

Table 8 Results summary for the three scenarios

From: Feasibility-sustainability study of power generation using solar energy at an industrial site: a case study from Egypt

 

S1

S2

S3

No. of PV panels

1771

1840

1771

Area (m2)

4627

4753

4627

No of inverters

13

8

13

No of strings

77 (each with 23 PV modules in series)

115 (each with 16 PV modules in series)

77 (each with 23 PV modules in series)

System losses (kwh/kWp/day)

0.07

0.09

0.09

Annual electricity production (MWh/year)

1,634

1,626

2,047

NPV (USD)

414,110.12

385,003.97

476,530.23

Discounted payback period (years)

5.711

5.988

6.139

LCOE (USD/kWh)

0.022

0.024

0.025

Total installation emissions (tCO2)

1726.31

1728.88

1942.72

Avoided CO2 emissions (tCO2)

14,898.993

15,808.960

18,891.435